負(fù)荷分配控制在壓縮機(jī)網(wǎng)絡(luò)中,壓縮機(jī)通常并聯(lián)運(yùn)行,有時也有串聯(lián)運(yùn)行形成網(wǎng)絡(luò)運(yùn)行的目的包括:備份靈活操作增加額外的能力通常注重單元機(jī)組的運(yùn)行而忽略網(wǎng)絡(luò)的優(yōu)化控制壓縮機(jī)制造商通常集中于單元機(jī)組的控制。從“網(wǎng)絡(luò)”的觀點(diǎn)來看,應(yīng)實(shí)現(xiàn)優(yōu)良的喘振保護(hù)和網(wǎng)絡(luò)的負(fù)荷分配優(yōu)化控制。壓縮機(jī)網(wǎng)絡(luò)
并聯(lián)機(jī)組控制系統(tǒng)的目標(biāo)是:保持主性能變量穩(wěn)定(壓力或流量)將負(fù)荷優(yōu)化分配到網(wǎng)絡(luò)中的各臺機(jī)組上,同時:發(fā)生喘振的機(jī)率最低。最低的能耗在啟動或停開單一機(jī)組時將所帶來的工藝擾動降到最低。壓縮機(jī)網(wǎng)絡(luò)ProcessPIC11UICVSDSCompressor12UICVSDSCompressor2HIC1Suctionheader用于調(diào)節(jié)負(fù)荷的壓縮機(jī)滿負(fù)荷運(yùn)轉(zhuǎn)的壓縮機(jī)注:所有控制系統(tǒng)均為獨(dú)立運(yùn)行變送器未標(biāo)明?;矩?fù)荷法Rc,1qr,12Rc,2qr,22Compressor1Compressor2MachinesoperateatsameRcsincesuctionanddischargeofbothmachinesaretiedtogetherPIC-SPBaseloadoneormorecompressorsandlettheother(s)absorbtheloadswingsSwingmachineBasemachineBasemachineisfullyloadedandrunswithoutrecycleQC,2=
QP,2SwingmachinecanberunningwithrecycleQC,1QP,1where:QP=FlowtoprocessQC=TotalcompressorflowQC-QP=RecycleflowLoadcouldbere-dividedtoeliminaterecycleQP,1QP,1+
QP,2
=
QP,1+
QP,2注:基本負(fù)荷法效率較低?;矩?fù)荷法增加了#1壓縮機(jī)組發(fā)生喘振的危險性,這是由于#1壓縮機(jī)將獨(dú)立承擔(dān)調(diào)整任何擾動?;矩?fù)荷法需要操作人員的經(jīng)常干預(yù)?;矩?fù)荷法并不是推薦的方式基本負(fù)荷法控制QP,2ProcessPIC11UICCompressor1VSDSCompressor2SuctionheaderNotesPerformancecontrollersactindependentofantisurgecontrolHighercapitalcostduetoextraFlowMeasurementDevices(FMD)HigherenergycostsduetopermanentpressurelossacrossFMD’s1FIC2FIC2UICoutoutRSPRSPRSPoutRSPEqualFlowDivisionLoadsharing
FlowDiagramforControlProcessVSDSMachine2operateswithrecyclewhilemachine1stillhasturndownMachinesoperateatsameRcsincesuctionanddischargeofbothmachinesaretiedtogetherEqualflowdivisionmightworkifbothmachinesareidenticalMachinesareneveridenticalexceptbycoincidenceBiasrelayonremotesetpointwouldonlyworkifcurveshavesamesteepnessNotes:RequiresadditionalcapitalinvestmentinFMD’sRequiresadditionalenergyduetopermanentpressurelossacrossFMD’sPoorpressurecontrolduetopositivefeedbackincontrolsystem(seenext)EqualflowdivisionisNOTrecommendedRc,1qr,12Rc,2qr,22PIC-SPQP,1QP,2QC,2EqualflowEqualflowQP,1=
QP,2EqualFlowDivisionLoadsharing
ParallelCompressorControlCompressor1Compressor2where:QP=FlowtoprocessQC=TotalcompressorflowQC-QP=RecycleflowQ2RcN1N3N2Inatypicalmaster-slavecontrolschemetheslaveneedstobeapprox.5timesfasterthanthemasterAThemachineisoperatinginpointAThisistheintersectionof4lines:ResistancelineR1PerformancecurveN1PIC-SPFIC-SP=OutputofPICR1PIC-SPFIC-SPProcessdisturbancecausestheresistancetochangefromR1toR2R2AsaresultthemachinemovestopointBBSincethePICisslowitdoesnotmoveitsoutputyetwhichistheFIC-SPTheFICreactsfastandwilltrytomaintainitsSPTheFICwillspeedupthemachinetopointCatspeedN3CThedisturbanceisamplifiedPositivefeedbacksystemOnlyasthePICstartstoreduceitsoutputtocontrolpressuretheFIC-SPcomesdownandthepressureisrestoredDNotesCausesinstabilitynearsurgePoorpressurecontrolduetopositivefeedbackincontrolsystemPIC1OUTRSPFIC1OUTRSPMasterSlaveSIC1DynamicResponse/
PressureToFlowCascadePressurecontroller(PIC)providesRemoteSetPoint(RSP)forFlowcontroller(FIC)TheFICprovidestheRSPforthespeedcontroller(SIC),suctionthrottlevalveorguidevanesThePICisthemasterandtheFICistheslaveMasterSlaveNotesAllcontrollersarecoordinating controlresponsesviaaserialnetworkMinimizesrecycleunderalloperatingconditionsProcess1UICVSDSCompressor1VSDSCompressor2Suctionheader1LSIC2UICoutRSPSerialnetworkoutRSP2LSIC1MPICSerialnetworkSerialnetworkEquidistantLoadsharing
FlowDiagramforControlProcessMachinesoperateatsameRcsincesuctionanddischargeofbothmachinesaretiedtogetherPIC-SPTheDEVisadimensionlessnumberrepresentingthedistancebetweentheoperatingpointandtheSurgeControlLineLinesofequalDEVcanbeplottedontheperformancecurvesasshown0.10.20.3DEV=00.10.20.3MachinesarekeptatthesamerelativedistancetotheSurgeControlLine(SCL)ThismeansinpracticethesameDEVforbothmachinesDEV1DEV2RecyclewillonlystartwhenallmachinesareontheirSCLSinceDEVisdimensionlessallsortsofmachinescanbemixed:small,big,axials,centrifugalsTheDEVwillbethesameforallmachinesbuttheywilloperateatdifferentspeedsandflowratesSCL=SurgeControlLineRc,1qr,12Rc,2qr,22Compressor1Compressor2Dev1=Dev2Q1=
Q2N1=N2Notes:Maximumturndown(energysavings)withoutrecycleorblow-offMinimizestheriskofsurgesinceallmachinesabsorbpartofthedisturbanceAutomaticallyadaptstodifferentsizemachinesCCCpatentedalgorithmEquidistantLoadsharing
ParallelCompressorControlLoadsharingControllerLoopDecouplingFAModePIRTLoop
Decoupling+Antisurge
ControllerAnalogInputs+DEVToantisurgevalveToperformancecontrolelementPrimaryresponseDEVDEVPrimaryresponseToperformancecontrolelementDEV>0Don’tchangeoutputxYesNoPrimaryresponsePrimaryresponseDon’tchangeoutputNoxYesApplyloadsharinggainToantisurgevalve
DEV£0CompressorsinParallel
theprimaryresponseMasterControllerPVSPPIDMastercontrollercontrolsthemainProcessVariable(PV)viaitsPIDcontrolblockTheoutputofthemastercontrollerPIDgoestotheprimaryresponseblockintheloadsharingcontrollerIntheprimaryresponseblockthecontrollerchecksifthemachineisclosetotheSCL:Yes:don’treducecapacity-keepoutputconstantNo:reducecapacityasnecessaryApplyloadsharinggainM0TheoutputofthemastercontrollergoesviatheprimaryresponseblockdirectlytotheperformancecontrolelementInordertocheckifthemachineisclosetotheSCLtheprimaryresponseblockneedstheDEVTheDEVisreportedbytheantisurgecontrollerWhenthemachineisclosetotheSCLthemastercontrollerwillnolongerreduceperformancetocontroltheprimaryvariableThemastercontrollerwillstarttoopentherecyclevalvetocontroltheprimaryvariableIfDEV<=0applyloadsharinggainOutputgoestoantisurgevalveLoopDecouplingFAModePILoopDecoupling+AnalogInputs+DEVToantisurgevalveToperformancecontrolelementPIDLoadbalancingPVPVSPPrimaryresponseDEVDEVDEVDEVfromotherloadsharingcontrollersPrimaryresponseAverageSPTheloadbalancingresponseLoadsharingControllerAntisurgeControllerMasterControllerThefastmastercontrollercontrolstheprimaryprocessvariablebydirectlymanipulatingthefinalcontrolelementsInordertobalancethemachinestheyneedtobekeptatthesameDEVTheantisurgecontrollerreportstheactualDEVtotheloadbalancingblockintheloadsharingcontrollerThisreportedDEVbecomestheProcessVariable(PV)fortheloadbalancingPIDloopTheloadsharingcontrollerreportsthisDEVPValsotothemastercontrollerOtherloadsharingcontrollersalsoreporttheirDEVPVtothemastercontrollerThemastercontrollercalculatestheaverageofallreportedDEVPV’sThisaverageDEVissentouttoallloadsharingcontrollerstobecometheSPforallloadbalancingblocksTheloadbalancingblockisaslowcontrollerthatwillequalizeallDEV’sforallparallelcompressorsItsoutputisaddedtothetotaloutputtotheperformancecontrolelementRTThePressureOverrideControl(POC)responseWhenalargedisturbanceoccursitcanhappenthattheperformancecontrolelement(e.g.speed)istooslowtokeepthepressureundercontrolTheoperatingpointridesthecurveandthepressurerisessharplyThereisahighchancetoexceedthereliefvalvesettingandtriptheprocessTheCCCmastercontrollerhasaPressureOverrideControl(POC)modethatwillopentheantisurgevalvetogetthedisturbanceundercontrolquicklyOpeningoftheantisurgevalveismuchfasterthanareductioninspeedAssoonastheoperatingpointdropsunderthePOC-SPlinetheantisurgevalvesstarttocloseagainTheprimaryPIDloopwillstabilizetheoperatingpointonthePIC-SPlineBenefitsFastresponseduringfastupsetsAvoidprocesstripsduetolackofresponseinperformancecontrolelementsAllowscloseroperationtoprocesslimitswithout takingriskLoopDecouplingFAModePILoopDecoupling+AnalogInputs+DEVToantisurgevalveToperformancecontrolelementPIDLoadbalancingPVPVSPPrimaryresponseDEVDEVDEVDEVfromotherloadsharingcontrollersPrimaryresponseAverageSPLoadsharingControllerAntisurgeControllerMasterControllerRTPI(One-Sided)SPPVPOC-SPRcqr2PIC-SPReliefvalvesettingProcess1AUICVSDSSection1VSDSSection1SuctionHeaderALSICoutRSPSerialnetworkRSPBLSIC1MPICSerialnetworkSerialnetworkSection2Section22AUIC1BUIC1BUICSerialnetworkSerialnetworkoutTrainBTrainAHowtooperateequidistantfromtheSurgeControlLine(SCL)whenthereismorethanonesectionpermachine???Selectpertrain--intheloadsharingcontroller--thesectionclosesttotheSCLByselectingthesectionclosesttotheSCLitisguaranteedthattheothersectiononthesametrainisnotinrecycleEquidistantLoadsharing
formulti-sectioncompressorsSharetheload--equalDEV’sforbothtrains--onthesectionclosesttotheSCLLoadsharingControllerLoopDecouplingLoadbalancingFAModePIRT+AntisurgeControllerAnalogInputsAverage+SPPVDEVfromotherloadsharingcontrollersDEV1Toantisurgevalve-1ToperformancecontrolelementPIDPVSPPrimaryresponseBothantisurgecontrollersreporttheirDEVtotheloadsharingcontrollerDEV1PI(One-Sided)SPPVPrimaryresponseFAModePIRTLoopDecoupling+AntisurgeControllerDEV2Toantisurgevalve-2DEV2PrimaryresponseThelowestDEVisselected:thesectionclosesttotheSCL<TheselectedDEVisreportedto:PrimarycontrolresponseblocksLoadbalancingblockMastercontrolleraveragingblockSelectingthesectionclosesttoSCLforparalleloperationMasterControllerLoopDecouplingMainselectioncriteriaforFMDinantisurgecontrolsystem:RepeatabilitySufficientsignal-to-noiseratioAccuracyoftheFMDisnotcriticalFMDdelaysmustbeabsolutelyminimalPresentstate-of-the-artlimitsthechoiceofFMDtoheadflowmetersortootherdevicesthatarebasedontheprincipleofvelocitymeasurement:OrificeplatesVenturi’sPitottubesetc.RecommendedflowrangeforFMDandtransmitterismaximumcompressorflowRecommended
DpcorrespondingtoQmax,compressoris10”WC(250mmH2O)ormoreFlowMeasuringDevice
(FMD)selectioncriteriaThepreferredlocationoftheFMD:SuctionofcompressorAsclosetotheinletflangeaspossibleVSDSCompressorDischargeSuctionminimumpossibleLesspreferablelocationoftheFMD:DischargeofcompressorAsclosetothedischargeflangeaspossibleminimumpossibleSelectionofthelocationshouldbebasedon:NecessityofsurgedetectionOftenmoredifficultwithflowmeasuredindischargeCapitalcostofflowmeasuringdeviceOperatingcostoftheFMD(permanentpressureloss)FlowMeasuringDevice
(FMD)locationThespeedofapproachingsurgeishighThetransmittertypeandbrandshouldbeselectedbasedontwomajorfactors:ReliabilitySpeedofresponseDesiredrisetimefor
Dp(flow)transmittersis200msorlessPressurestepis100%Thefirstorderresponse(63%)islessthan200msDesiredrisetimeforpressuretransmittersis500msorlessResponsetimeofthe
FMDtransmitter
Inonly400ms,DPOdroppedby14%,witha2%changein
DPc100%0100%0100%01SEC.DPoACDBPdACDBDPcACDBTimeActualpressureTransmitteroutput63%response1-(1/e)t1islessthan200msKnowingtheflowisessentialtodeterminethedistancebetweentheoperatingpointandtheSCLDampingthe
Dpo
(flow)transmitterdestroysessentialinformationDampingthe
Dpo
(flow)transmittercanparalyzethecompleteantisurgecontrolsystem!!!Theeffectofdamping
theDpo
(flow)transmitter500-5001.252.503.755Time(seconds)FlowStartofSurgeActualFlowt=16.0st=1.70st=0.20st=0.03sCriteriaforantisurgevalvesizingbasedonCCC’sexperienceProvideadequateantisurgeprotectionforworstpossibledisturbancesProvideadequateantisurgeprotectioninalloperatingregimesSizedtoprovideflowpeaksgreaterthanwhatisrequiredinsteadystatetooperateontheSurgeControlLineSizedtoavoidchokezoneNotbeoversizedfromcontrollabilitypointofviewTakepointAattheintersectionofthemaximumspeedperformancecurveandtheSurgeLimitLine(SLL)Calculate
Cv,calc(orequivalent)forpointASelectstandardvalvesizeusingthefollowingcriteria:1.8.Cv,calc<Cv,selected<2.2.Cv,calcRcQvolASizingtheantisurgecontrolvalveARc
Analternativemethodyieldingexcellentresultsis:TakedesignpointofthecompressorpointADrawahorizontallinethroughthedesignpointTakepointBatintersectionofmaximumspeedperformancecurveandthehorizontallineBCalculateCv,calcinpointBSelectstandardvalvesizeusingthefollowingcriteria: 0.9.Cv,calc<Cv,selected<1.1.Cv,calcSizingtheantisurge
controlvalve-alternativemethodQvolAntisurgevalvestrokespeedAntisurgevalvemusthavespeedofresponseadequateforantisurgeprotectionforalldisturbancesRecommendedfullstroketimes:Size
Closetoopen
Opentoclose1”to4” 1second <3seconds6”to12” 2seconds <5seconds16”andup 3seconds <10secondsClosingtimeneedstobethesameorderofmagnitudetoassurethesameloopgaininbothdirectionsAntisurgevalvecharacteristicNormallycontrolvalvesareselectedtobeopen80%to90%fordesignconditionsAntisurgevalvescanoperateanywherebetween0%and100%Inordertohaveanequalloop-gainoverthewholeoperatingrangealinearvalveisrequiredThiswillallowforthefastesttuningleadingtosmallersurgemarginsStrokespeedandcharacteristicoftheantisurgevalveMostnormalcontrolvalvescanbemadetoperformasrequiredforantisurgecontrolThefollowingstepshelpimprovetheperformanceofthevalveInstallpositionerMinimizetubinglengthbetweenI/PandvalvepositionerInstallvolumeboosterMinimizevolumeandresistancebetweenvolumeboosterandactuatorIncreaseairsupplylineto3/4”ormoreIncreasesizeofairconnectionintotheactuatorDrilladditionalholesinactuator-avoidspullingavacuumImprovingtheperformanceoftheantisurgevalvePipinglay-outinfluencesthecontrollabilityofthethetotalsystemTheprimaryobjectiveoftheantisurgecontrolleristoprotectthecompressoragainstsurgeThisisachievedbyloweringtheresistancethecompressorisfeelingTheresistanceisloweredbyopeningtheantisurgevalveDead-timeandtime-laginthesystemneedstobeminimizedThisisachievedby minimizingthe volumebetween threeflangesDischargeflangeof thecompressorRecyclevalveflangeCheckvalveflangeVSDSCompressor1volumetobeminimizedPipinglay-outconsiderationwhendesigninganantisurgecontrolsystemSection1Section2Inordertoprotectsection1theantisurgevalveneedstobeopenedThevolumebetweencompressordischarge,checkvalveandantisurgevalvedeterminesthedeadtimeandlagtimeinthesystemLargevolumeLargevolumesignificantlydecreasestheeffectivenessoftheantisurgeprotectionResultPoorsurgeprotectionLargesurgemarginsEnergywasteProcesstripsbecauseofsurgeNote:ThisspecificpipinglayoutisfoundonmanywetgascompressorsinFCCU’sUsingasingleantisurgevalveincreasesrecyclelagtimeSection1Section2Thepipinglay-outforsection2isexcellentforsurgeprotectionMinimumvolumebetweenthethreeflangesSmallvolumeThepipinglay-outforsection1isnotidealLargevolumetobede-pressurizeddecreasesabilityofthecontrolsystemtoprotectthemachineagainstsurgeResultPoorsurgeprotectionLargesurgemarginsEnergywasteProcesstripsbecauseofsurgeSharingrecyclecoolers
degradessurgeprotectionCompressor1Compressor1hasidealpipinglay-outforsurgeprotectionMinimumvolumebetweenthethreeflangesCompressor2MinimumvolumeThepipinglay-outforcompressor2iscommonlyfoundintheindustryThecoolercreatesadditionalvolumeanddecreasestheeffectivenessoftheantisurgecontrolsystemIncreasedvolumeduetocoolerThepipinglay-outforcompressor2canbeacceptableiftheadditionalvolumedoesnotcreateexcessivedeadtimeandlaginthemResultIncreasedsurgemarginsEnergywasteInstallingrecyclevalveupstreamfrom
coolerimprovescontrolresponseCompressorhasidealpipinglay-outforsurgeprotectionMinimumvolumebetweenthethreeflangesforallsectionsRecyclelinesconfiguredforoptimumsurgeprotectionMinimumvolumeSection2Section3Section1ProcessSuctionLay-out#1hasminimumvolumebetweentheflangesandisthebestlay-outforantisurgecontrolpurposesSection2Section3Section1ProcessSuctionSection1Section2Section3SuctionProcessLay-out#1:CompressorwithrecyclelinesoptimallyconfiguredforantisurgecontrolLay-out#2:Compressorwithcoolersupstreamofrecycletake-offWhenselectinglay-out#2theresidencetimeofthegasinthe“surge”volumeshouldbeverifiedtocheckacceptabletimedelaysarenotexceededThesetwopipinglay-outsaremostcommonforantisurgecontrolLay-out#2requiresonecoolerlessandthusthecapitalinvestmentislowerLay-out#2willrequirebiggersurgecontrolmarginsWhichantisurgepipingconfigurationdoyouchoose???AnalogcontrollerSLLSCL100%0%Controlleroutput100%0%LeadingengineeringcontractorperformedevaluationofexecutiontimeinfluenceonabilitytoprotectcompressorfromsurgeDynamicsimulationofcompressorwasbuiltDigitalcontrollersarecomparedagainstanalogcontrolleronsimulationAnalogcontrollerhasnoexecutiontimeandisimmediateAnalogcontrollertunedforminimumovershootDigitalcontrollersgetexactsametuningparametersDigitalcontrollersgetexactsamedisturbanceOperatingpointTimeTimeInfluenceofcontroller
executiontimeAnalogcontrollerSLLSCL100%0%100%0%100%ControlleroutputOperatingpointDigitalcontroller(2exec
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 現(xiàn)場施工匯報材料范文
- 外墻鋁板幕墻施工圖紙審核方案
- 地鐵軌道工程施工質(zhì)量保證體系及措施
- 四年級數(shù)學(xué)幾百幾十?dāng)?shù)乘以一位數(shù)過關(guān)測驗(yàn)習(xí)題帶答案
- 城市土壤改良與施工方案
- 施工安全管理三方協(xié)議書模板
- 庭院工程設(shè)計合同協(xié)議書范文
- 《s理念知識培訓(xùn)》課件
- 航空維修廠環(huán)氧自流平地面施工方案
- 語文課件-神奇的路
- 2024年電商平臺入駐服務(wù)合同
- 2024年度政府采購代理服務(wù)合同-醫(yī)療衛(wèi)生設(shè)備采購項(xiàng)目3篇
- GJB9001C版標(biāo)準(zhǔn)培訓(xùn)課件
- 船舶防火與滅火(課件)
- 七、監(jiān)理工作重點(diǎn)、難點(diǎn)分析及對策
- 面膜中藍(lán)銅肽經(jīng)皮滲透性和改善皮膚衰老作用研究
- 湖北省荊州市八縣市2023-2024學(xué)年高一上學(xué)期1月期末考試 化學(xué) 含解析
- 專題05 說明文閱讀(必考題型梳理)50題-2023-2024學(xué)年八年級語文下學(xué)期期中專題復(fù)習(xí)(上海專用)(解析版)
- 聲光影的內(nèi)心感動:電影視聽語言學(xué)習(xí)通超星期末考試答案章節(jié)答案2024年
- 緊密型縣域醫(yī)共體信息化建設(shè)指南及評價標(biāo)準(zhǔn)
- 盤拉機(jī)操作手冊新
評論
0/150
提交評論