版權(quán)說明:本文檔由用戶提供并上傳,收益歸屬內(nèi)容提供方,若內(nèi)容存在侵權(quán),請進(jìn)行舉報或認(rèn)領(lǐng)
文檔簡介
3目
錄第一章臨時用電設(shè)施1配電室···············································································12配電箱·············································································23配電箱防護(hù)棚·······························································34配電線路········································································4電纜埋地敷設(shè)····························································4電纜明敷設(shè)···································································5樓層配電·······································································6線纜進(jìn)配電箱做法······················································75防雷及接地······································································8配電箱接地···································································8塔吊接地·······································································9固定加工機(jī)械接地···················································10腳手架接地··································································11臨時鋼制房接地·························································126現(xiàn)場照明·········································································13施工區(qū)照明·································································13鏑燈架········································································13LED施工照明燈······················································14正式照明替代臨時照明·······································156.1.4地下室臨時照明·····························································16辦公區(qū)照明·········································································17生活區(qū)照明及冷暖空調(diào)用電·········································187其他用電················································································19設(shè)備安全用電·····································································19電焊機(jī)用電··········································································20USB手機(jī)充電·····································································21第二章臨時用水設(shè)施1消防泵房··············································································222水箱·························································································233樓層消防敷設(shè)····································································244消火栓··················································································255洗車池····················································································266雨水收集池☆·····································································277噴霧降塵系統(tǒng)······································································288生活區(qū)臨水設(shè)施(1)☆·················································299生活區(qū)臨水設(shè)施(2)☆·················································304臨時用電設(shè)施1配電室基本要求位置:靠近電源,無腐蝕介質(zhì)且道路通暢;設(shè)置要求:配電室材料耐火等級不低于3級,空間應(yīng)滿足規(guī)范要求,自然通風(fēng)有防止雨雪侵入和動物進(jìn)入措施門外開;消防:室內(nèi)配置砂箱和可用于撲滅電氣火災(zāi)的滅火器,分別設(shè)置正常照明和應(yīng)急照明燈;設(shè)置警示標(biāo)志,聯(lián)系人和聯(lián)系電話。配電室內(nèi)總配電箱要高出地面20cm,配電箱后門須有操作空間,離墻距離應(yīng)不小于1m,配電室凈空高度不小于3m。同時進(jìn)出電纜需設(shè)置電纜溝,溝內(nèi)填充細(xì)沙。配電室應(yīng)有重復(fù)接地,接地電阻值應(yīng)符合要求。配電室地面素水泥地面磨平,無雜物,無積水。操作面鋪設(shè)絕緣踏板或膠墊。配電室設(shè)計圖配電室實(shí)體圖片5配電箱責(zé)任牌一級配電箱二級配電箱三級配電箱2配電箱基本要求:選用的配電箱應(yīng)符合國家標(biāo)準(zhǔn)和地方要求。選用的電器元件應(yīng)有生產(chǎn)許可證和產(chǎn)品合格證。總配電箱、開關(guān)箱應(yīng)設(shè)置漏電保護(hù)裝置。其中,總配電箱漏電保護(hù)器額定漏電動作電流>30mA、額定漏電動作時間>0.1s;開關(guān)箱漏電保護(hù)器額定漏電動作電流≤30mA、額定漏電動作時間≤0.1s。配電箱應(yīng)注明編號、責(zé)任單位、責(zé)任人和聯(lián)系電話,箱內(nèi)張貼配電線路圖、巡檢記錄。配電箱尺寸大小及配置參照集團(tuán)公司標(biāo)準(zhǔn)圖冊。配電箱責(zé)任牌,雙門配電箱為150*150mm,單門配電箱為100*100mm。藍(lán)底白字。字體為宋體,字體大小雙門為36號,單門為28號。臨時用電設(shè)施3配電箱防護(hù)配電箱防護(hù)棚應(yīng)采用工具式,由型鋼或剛管制作,置于混凝土承臺上,承臺中部留置400mm寬溝槽,防護(hù)棚內(nèi)操作空間符合規(guī)范要求;頂部采用雙層硬防護(hù)(間距500mm),頂部防砸,底部防雨(有坡度),雙層框架外圍包1mm厚鋼板,鋼板應(yīng)采用戶外車貼形式粘貼安全標(biāo)語、標(biāo)識、編號,標(biāo)語為藍(lán)(中建藍(lán))底白字,上、下弦張貼50mm寬黃黑警示色;配電箱下部應(yīng)對進(jìn)出電纜線采取絕緣套管保護(hù),并做相應(yīng)標(biāo)注區(qū)分進(jìn)出線,操作面鋪設(shè)絕緣踏板或膠墊,外側(cè)配備消防器材。臨時用電設(shè)施配電線路電纜埋地敷設(shè)埋深不小于0.7米,在電纜周圍敷設(shè)不小于5厘米厚細(xì)沙,覆蓋磚或硬質(zhì)保護(hù)層,過路時穿保護(hù)管;易受破壞的場所選用鎧裝電纜。電纜引出地面時,從2米高至地下20厘米處,必須加設(shè)防護(hù)套管;套管內(nèi)徑不小于電纜外徑的1.5倍。埋地電纜的接頭應(yīng)設(shè)在地面上的接線盒內(nèi),接線盒應(yīng)防雨、水浸入并遠(yuǎn)離易燃易爆、易腐蝕場所。在地面上,沿電纜走向路徑設(shè)電纜警示標(biāo)志牌,間距15-20米,轉(zhuǎn)角處也必須設(shè)置。電纜標(biāo)識牌電纜埋地做法臨時用電設(shè)施4.2電纜明敷設(shè)基本要求:電纜沿地面明敷時應(yīng)設(shè)置保護(hù)槽,保護(hù)槽應(yīng)與地面固定,并設(shè)置明顯警示標(biāo)識。采用鋼絲繩做吊索,將電纜用PVC管進(jìn)行間隔固定,其間距為0.5米左右;吊索吊架間距不大于12米。電纜垂直敷設(shè)的位置應(yīng)充分利用在建工程的豎井、垂直孔洞等,并應(yīng)靠近負(fù)荷中心,固定點(diǎn)每層不得少于一點(diǎn),水平向電纜線敷設(shè)應(yīng)在墻體2.5m以上做支架架設(shè),固定點(diǎn)應(yīng)絕緣保護(hù);臨時用電設(shè)施電纜明敷保護(hù)槽電纜吊索吊架安裝4.3樓層配電基本要求:電纜線穿越建筑物、構(gòu)筑物、道路、易受機(jī)械損傷的場所及引出地面從2m高度至地下200mm處,應(yīng)加設(shè)防護(hù)套管;電纜垂直敷設(shè)的位置應(yīng)充分利用在建工程的豎井、垂直孔洞等,并應(yīng)靠近負(fù)荷中心,固定點(diǎn)每層不得少于一點(diǎn),水平向電纜線敷設(shè)應(yīng)在墻體2.5m以上做支架架設(shè),固定點(diǎn)應(yīng)絕緣保護(hù);水平敷設(shè)宜采用三角支架或鋼索進(jìn)行高掛,高度不得低于2.5m,若因作業(yè)限制無法高掛的,可沿墻角、地面敷設(shè),但應(yīng)采取防機(jī)械損傷措施,并設(shè)警示標(biāo)識;樓層內(nèi)固定式配電箱應(yīng)考慮做重復(fù)接地,接地體應(yīng)預(yù)埋,重復(fù)接地豎向距離不大于20m(每5層)做一處。樓層配電箱位置設(shè)置應(yīng)就近主電纜,原則不超過3m。臨時用電設(shè)施4.4線纜進(jìn)配電箱做法基本要求:電纜線引出地面從2m高度至地下200mm處,應(yīng)加設(shè)防護(hù)套管;嚴(yán)禁電線、電纜明露。采用軟套管進(jìn)配電箱應(yīng)成排成列,排列均勻,并有固定措施。采用硬質(zhì)塑料管做套管,應(yīng)按硬質(zhì)塑料管做法施工,做到橫平豎直,排列整齊,固定措施到位。電纜進(jìn)配電箱軟套管做法實(shí)體圖電纜進(jìn)配電箱硬套管做法實(shí)體圖臨時用電設(shè)施防雷及接地配電箱接地基本要求:施工現(xiàn)場一、二級配電箱柜應(yīng)有良好的重復(fù)接地聯(lián)結(jié)。當(dāng)接地電阻值不能滿足使用要求時,應(yīng)增設(shè)接地裝置。配電箱防護(hù)棚要與接地干線聯(lián)結(jié)。配電箱門需從接地PE排引出與箱門聯(lián)結(jié)。配電箱PE排需從接地干線引出接地線聯(lián)結(jié)。配電箱箱門、支架、防護(hù)棚都應(yīng)直接從接地干線或PE排聯(lián)結(jié),不得串接。接地聯(lián)結(jié)用的接地線應(yīng)為軟BVR銅線或軟編織銅線,接線端子用開口線鼻壓接。防護(hù)棚可通過扁鋼焊接,需做好防腐處理。配電箱防護(hù)接地示意圖配電箱接地臨時用電設(shè)施5.2塔吊接地基本要求:施工現(xiàn)場的塔吊應(yīng)有良好的防雷接地措施。塔吊接地需做硬聯(lián)結(jié),通過預(yù)留的接地扁鋼(可從主體正式接地體引出)與塔吊基礎(chǔ)底座焊接。預(yù)留接地扁鐵不小于40*4mm或接地截面不小于
160mm2。焊接倍數(shù)為扁鋼的2倍寬度,三面施焊,焊接處并做好防腐處理。接地扁鋼需預(yù)留斷接點(diǎn),供塔吊接地電阻測試。臨時用電設(shè)施塔吊基礎(chǔ)接地示意圖5.3固定加工機(jī)械接地基本要求:施工現(xiàn)場的固定加工機(jī)械應(yīng)有良好的接地聯(lián)結(jié)。當(dāng)接地電阻值不能滿足使用要求時,應(yīng)增設(shè)接地裝置。在加工場地面施工前預(yù)埋接地扁鐵俺敷設(shè)至各加工設(shè)備處。小型機(jī)械接地應(yīng)采用軟聯(lián)結(jié),可通過預(yù)埋扁鐵鉆孔,用軟銅線BVR,截面不小于10mm2的接地線聯(lián)結(jié)至設(shè)備外殼。注:因各地對加工機(jī)械接地要求不同,此做法北京地區(qū)執(zhí)行,外地參照當(dāng)?shù)匾髮?shí)施,可參考此做法。臨時用電設(shè)施加工機(jī)械接地示意圖加工機(jī)械接地示意圖5.4腳手架接地基本要求:施工現(xiàn)場的落地腳手架應(yīng)有良好的防雷接地措施。做法:通過建筑物內(nèi)正式工程接地系統(tǒng)引出接地點(diǎn),與腳手架橫立桿聯(lián)結(jié)。聯(lián)結(jié)點(diǎn)間距應(yīng)不大于15m設(shè)置,且不少于四個角設(shè)置。腳手架接地需做硬聯(lián)結(jié),通過預(yù)留的接地扁鋼(可從主體正式接地體引出)與腳手架橫縱桿焊接。焊接處做好防腐與標(biāo)識。預(yù)留接地扁鐵不小于25*4mm或接地截面不小于
100mm2。焊接倍數(shù)為扁鋼的2倍寬度,三面施焊,焊接處并做好防腐處理。腳手架接地點(diǎn)應(yīng)做好接地標(biāo)識。防止破壞及便于檢查。臨時用電設(shè)施腳手架接地示意圖5.5臨時鋼制房接地基本要求:施工現(xiàn)場及生活區(qū)的臨時辦公用房、生活區(qū)用房采用鋼制材質(zhì)時,應(yīng)有良好的防雷接地措施。在鋼制板房四角處預(yù)留接地點(diǎn)。用不小于Ф10鍍鋅圓鋼與鋼制板房基礎(chǔ)聯(lián)結(jié),并在屋頂四角做高出房頂500mm的避雷針。避雷針與接地點(diǎn)貫通聯(lián)結(jié)。臨時用電設(shè)施鋼制房接地實(shí)體圖現(xiàn)場照明基本要求:在潮濕和易觸及帶電體場所內(nèi),照明采用不大于36V的安全電壓,樓梯內(nèi)及地下室照明線路可借用正式的機(jī)電預(yù)留管線進(jìn)行布線。滿足節(jié)能環(huán)保要求,燈具應(yīng)優(yōu)先選用節(jié)能燈具,如:LED燈、太陽能燈等。施工區(qū)照明鏑燈架燈架整體為藍(lán)色,由基礎(chǔ)部分、標(biāo)準(zhǔn)節(jié)、平臺和連接件組成,標(biāo)準(zhǔn)節(jié)截面尺寸500×500mm,高1800mm;燈架應(yīng)設(shè)接地裝置,上下節(jié)做好跨接接地。燈架基礎(chǔ)底座采用混凝土澆筑磨平,尺寸大小為(長×寬×高)700×700×300mm;臨時用電設(shè)施LED施工照明燈基本要求:施工現(xiàn)場夜間照明可在塔吊等較高的地方設(shè)置LED(聚光型)燈具。施工照明燈具需有控制措施(一塔一控),方便開啟和關(guān)閉,做到節(jié)能。施工道路具備條件的可選用太陽能燈具。—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—鏑燈與LED燈費(fèi)用分析:鏑燈:燈具單價+燈具功率*每天使用時間*施工工期*電費(fèi)*電損500+3.5*10*200*1*1.05=7850(元)LED燈:燈具單價+燈具功率*每天使用時間*施工工期*電費(fèi)*電損2000+0.5*10*200*1*1.05=3050(元)臨時用電設(shè)施LED燈具實(shí)體圖太陽能燈具實(shí)體圖6.1.3正式照明替代臨時照明正式照明替代臨時照明,主要是利用建筑物內(nèi)正式預(yù)埋管路,通過穿正式電線,涮錫并頭并做好絕緣與防水防護(hù)后,接臨時燈具提供照明。一般在有通道和地下室需要照明且安裝高度超過臨電規(guī)范要求2.5米以上的地方實(shí)施。臨時用電設(shè)施正式照明替代臨時照明實(shí)體圖6.1.4地下室臨時照明在不具備正式照明替代臨時照明的部位,可采用低壓照明,優(yōu)先選用LED節(jié)能燈具,布線要整齊美觀,支架間距不超過6米,線路應(yīng)固定在瓷瓶上,線纜平直。臨時用電設(shè)施臨時燈具實(shí)體圖臨電線路布置圖6.2辦公區(qū)照明基本要求:辦公區(qū)照明應(yīng)選用節(jié)能燈具。在走廊等公共區(qū)域宜使用LED燈泡。在辦公室、會議室等室內(nèi)宜使用LED燈盤?!?/p>
—
—
—
—
—
—
—
—
—
—
—
—
—
—LED燈具與普通燈具費(fèi)用分析:T5熒光燈管:房間數(shù)*每間燈具數(shù)*燈具功率*每天使用時間*施工工期*電費(fèi)單價+燈具費(fèi)用16*2*0.036*10*600*1+16*2*30=7872(元)LED燈具:房間數(shù)*每間燈具數(shù)*燈具功率*每天使用時間*施工工期*電費(fèi)單價+燈具費(fèi)用16*2*0.018*10*600*1+16*2*50=5056(元)辦公區(qū)走廊照明采用LED燈泡會議室及辦公室照明采用LED燈盤臨時用電設(shè)施6.3生活區(qū)照明及冷暖空調(diào)用電生活區(qū)照明應(yīng)選用節(jié)能燈具。同時應(yīng)使用
36V低壓照明。生活區(qū)設(shè)置冷暖空調(diào)的用電,應(yīng)單獨(dú)設(shè)置
220V電源回路在配電箱集中控制,空調(diào)回路管線及空調(diào)插座均設(shè)置在室外??照{(diào)插座應(yīng)有防水
盒,高度不低于1.8m??照{(diào)室外機(jī)應(yīng)采用支架固定,首層支架高度大于30cm??照{(diào)室外機(jī)應(yīng)排列整齊,管線一致。宿舍內(nèi)照明采用36V低壓LED燈泡生活區(qū)空調(diào)管線及支架實(shí)例圖臨時用電設(shè)施其他用電設(shè)備安全用電基本要求:設(shè)備與電源距離設(shè)置設(shè)備開關(guān)箱箱體中心距地面垂直高度不低于
1.4m;設(shè)備水平負(fù)荷線應(yīng)采用PVC或軟管埋地敷設(shè);設(shè)備距開關(guān)箱水平距離不得大于3m設(shè)備接線示意圖臨時用電設(shè)施7.2電焊機(jī)用電基本要求:電焊機(jī)一側(cè)電源線長度不應(yīng)大于5m,二側(cè)焊把線長度不應(yīng)大于30m;電焊機(jī)外殼應(yīng)做保護(hù)接零;電焊機(jī)應(yīng)設(shè)置電焊機(jī)專用開關(guān)箱,交流電焊機(jī)專用箱內(nèi)應(yīng)包含隔離開關(guān)、漏電開關(guān)以及二次側(cè)觸電保護(hù)器;露天冒雨不得從事電焊作業(yè);電焊機(jī)一側(cè)、二側(cè)接線處防護(hù)罩應(yīng)齊全;焊機(jī)吊斗尺寸應(yīng)根據(jù)焊機(jī)尺寸確定,骨架采用L40角鋼焊接制作,骨架內(nèi)鋼筋直徑為Φ14~Φ16,豎向鋼筋間距不大于150mm,居中位置設(shè)置鋼筋門,上鎖,四角焊接Φ16鋼筋吊環(huán),上蓋采用鍍鋅鐵皮瓦。焊機(jī)專用箱固定于吊斗外側(cè),并配備滅火器材。交流焊機(jī)專用箱內(nèi)應(yīng)包含隔離開關(guān)、漏電開關(guān)以及二次側(cè)漏電保護(hù)器。電焊機(jī)接線示意臨時用電設(shè)施7.3
USB手機(jī)充電基本要求:生活區(qū)設(shè)置USB手機(jī)充電插座,可避免在生活區(qū)設(shè)置
220V電源插座。USB插座面板安裝高度1.3m,每房間根據(jù)床位建議設(shè)置4~6個插座。專用手機(jī)USB充電插座圖臨時用電設(shè)施1消防泵房基本要求:材料:使用不燃材料支搭,列為重點(diǎn)防火部位,設(shè)重點(diǎn)防火標(biāo)識牌、防火管理制度和值班制度;消防泵宜設(shè)置自動啟動裝置,不應(yīng)少于兩臺,互為備用,高度超過100m的在建工程,應(yīng)增設(shè)臨時中轉(zhuǎn)水池及加壓水泵,中轉(zhuǎn)水池的有效容積不應(yīng)少于10m3,出水管管徑不應(yīng)小于DN100;消防泵房應(yīng)獨(dú)立供電,消防配電線路應(yīng)自施工現(xiàn)場總配電箱的總斷路器上端接入,且應(yīng)保持不間斷供電;消防泵房應(yīng)配置通訊設(shè)備及啟動流程圖,配備應(yīng)急照明燈。消防泵房實(shí)體圖臨時用水設(shè)施消防系統(tǒng)圖2水箱基本要求:水箱大小應(yīng)滿足臨時消防及臨時用水計算需求。水箱應(yīng)設(shè)置水位計及自動補(bǔ)水裝置。北方水箱應(yīng)有防凍措施,南方看當(dāng)?shù)貤l件定。水箱制作可采用成品組裝不銹鋼水箱或鋼板焊接,采用鋼板焊接水箱,鋼板厚度不小于8mm。焊縫均勻,無滲漏,鋼板及焊接處防腐處理完整。水箱實(shí)體圖臨時用水設(shè)施3
樓層消防管道敷設(shè)基本要求:消防管道應(yīng)成環(huán)形設(shè)置。管徑應(yīng)滿足臨水設(shè)計要求。消防豎管的管徑應(yīng)該根據(jù)在建工程臨時消防用水量、豎管內(nèi)水流計算速度計算確定,且不應(yīng)小于DN100;與正式工程管徑應(yīng)設(shè)計一致。在建工程高度超過100m的,應(yīng)在適當(dāng)樓層增設(shè)臨時中轉(zhuǎn)水池及加壓水泵,確保消防用水,超高層二次蓄水池、二次加壓應(yīng)在90m左右實(shí)施,二次加壓泵宜設(shè)置自動啟動裝置;按照正式工程設(shè)計提前安裝部分正式消防管道以替代臨時消防官網(wǎng)使用,安裝臨時消火栓系統(tǒng)時可不考慮分區(qū)設(shè)計。主體工程施工時,臨時消火栓的環(huán)網(wǎng)設(shè)置在地下,利用正式消防管道按施工藍(lán)圖布置,再將
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 省級課題申報書模板
- 行政管理師考試實(shí)務(wù)操作技巧試題及答案
- 新技術(shù)在細(xì)菌檢測中的應(yīng)用試題及答案
- 衡陽課題申報書
- 微生物抗生素研究的前沿挑戰(zhàn)試題及答案
- 七年級語文下冊 第二單元 國家情懷 7 誰是最可愛的人教學(xué)設(shè)計 新人教版
- 項目管理專業(yè)考試真題試題及答案
- 幼兒籃球課題申報書
- 小學(xué)教師研修課題申報書
- 行政管理師職業(yè)生涯的持續(xù)發(fā)展與提升建議試題及答案
- 天耀中華合唱簡譜大劇院版
- 強(qiáng)制執(zhí)行股東分紅申請書
- 酒店前廳部溝通技巧
- 車隊事故分析報告總結(jié)
- 藥品追溯系統(tǒng)培訓(xùn)課件模板
- 工業(yè)園區(qū)的消防安全管理課件
- 2024信息安全意識培訓(xùn)ppt課件完整版含內(nèi)容
- 互聯(lián)網(wǎng)數(shù)據(jù)中心(IDC)業(yè)務(wù)介紹
- JGT366-2012 外墻保溫用錨栓
- 《界面圖標(biāo)設(shè)計》課件
- 2021阿里巴巴Java開發(fā)手冊1.4
評論
0/150
提交評論