1、房間編號(hào)房間編號(hào):面積(m2設(shè)計(jì)單位冷量w/m2設(shè)計(jì)總冷量kw設(shè)計(jì)單位熱量設(shè)計(jì)總熱量國(guó)祥型號(hào)首層:型號(hào)單位冷量kw數(shù)量(臺(tái) 1廚房233002ST 6.51200.78700.455KCR-200C 2.151 3ST7.041200.8448700.4928KCR-200C 2.151 4ST14.5120 1.7470 1.015KCR-200C 2.151 5宴會(huì)廳7203502527050.4KDC120-469.34 6辦公室7150 1.05700.49KCR-200C 2.151 7行李房71000.7700.49KCR-200C 2.151 8電梯廳551508.2570 3.

2、85KCR-1000C9.481 9酒店大堂21320042.67014.91KCR-1200C11.54 10商務(wù)中心20150370 1.4KCR-300C 3.261 11電梯廳42150 6.370 2.94KCR-800C7.321 12茶餐廳10930032.7707.63KCR-1200C11.53 13便利店23.5250 5.87570 1.645KCR-600C 5.81 14CD/文具店23.5250 5.87570 1.645KCR-600C 5.81 15面包店36250970 2.52KCR-1000C9.481 16廚房300070 2.117特色餐飲18250

3、4.570 1.26KCR-500C 4.851 18甜品店26250 6.570 1.82KCR-800C7.321 19西藥房20250570 1.4KCR-600C 5.81 20茶/煙/酒店20250570 1.4KCR-600C 5.81 21超市12625031.5708.82KCR-1200C11.53 22外廊234新風(fēng)降溫至24度,餐廳的新風(fēng)直接引入吊柜30二層2_1A中餐包房015830017.470 4.06KCR-1000C9.482 2_2B中餐包房02273008.170 1.89KCR-1000C9.481 2_3B中餐包房03273008.170 1.89KCR

4、-1000C9.481 2_4B中餐包房04273008.170 1.89KCR-1000C9.4812_5B中餐包房05273008.170 1.89KCR-1000C9.481 2_6B中餐包房0632.283009.68470 2.2596KCR-1200C11.51 2_7A中餐包房0767.3230020.19670 4.7124KCR-1200C11.52 2_8C中餐包房0840.0730012.02170 2.8049KCR-1200C11.51 2_9A中餐包房097830023.470 5.46KCR-1400C12.92 2_10B中餐包房107830023.470 5.

5、46KCR-1400C12.92 2_11B中餐包房11293008.770 2.03KCR-1000C9.481 2_12B中餐包房12293008.770 2.03KCR-1000C9.481 2_13B中餐包房13293008.770 2.03KCR-1000C9.481 2_14B中餐包房14293008.770 2.03KCR-1000C9.481 2_15A中餐包房156* 4.2KCR-1000C9.482 2_16D小宴會(huì)廳269.3130080.7937018.8517KDC070-4422 2_17A沐足房0113.64200 2.728700.9548KCR-300C 3

6、.261 2_18B沐足房0223.66200 4.73270 1.6562KCR-500C 4.851 2_19C沐足房0325.67200 5.13470 1.7969KCR-600C 5.81 2_20C沐足房0424.23200 4.84670 1.6961KCR-500C 4.851 2_21C沐足房0520.03200 4.00670 1.4021KCR-400C41 2_22C沐足房0637.112007.42270 2.5977KCR-800C7.321 2_23A沐足房0717.44200 3.48870 1.2208KCR-400C41 2_24A沐足房088.76200

7、1.752700.6132KCR-200C 2.151 2_25A沐足房098.8200 1.76700.616KCR-200C 2.151 2_26A沐足房1012.46200 2.492700.8722KCR-300C 3.261 2_27A沐足房1113.6200 2.72700.952KCR-300C 3.261 2_28A沐足房1212.45200 2.49700.8715KCR-300C 3.261 2_29A沐足房1313.62200 2.724700.9534KCR-300C 3.261 2_30A沐足房1410.29200 2.058700.7203KCR-200C 2.15

8、1 2_31A沐足房1511.53200 2.306700.8071KCR-300C 3.261 2_32A沐足房1610.69200 2.138700.7483KCR-200C 2.151 2_33A沐足房1711.9200 2.38700.833KCR-300C 3.261 2_34A沐足房1817.78200 3.55670 1.2446KCR-400C412_35A沐足房1913.12200 2.624700.9184KCR-300C 3.261 2_36A沐足房2017.78200 3.55670 1.2446KCR-400C41 2_37A沐足房2113.12200 2.62470

9、0.9184KCR-300C 3.261 2_38A沐足房2217.82200 3.56470 1.2474KCR-400C41 2_39A沐足房2312.94200 2.588700.9058KCR-300C 3.261 2_40A沐足房2412.42200 2.484700.8694KCR-300C 3.261 2_41A沐足房2512.94200 2.588700.9058KCR-300C 3.261外廊398新風(fēng)降溫至24度24三層KTV:3_1C型R3.01432309.8970 3.01KCR-1200C11.51 3_2C型R3.0230230 6.970 2.1KCR-800C

10、7.321 3_3C型R3.0330230 6.970 2.1KCR-800C7.321 3_4C型R3.0430230 6.970 2.1KCR-800C7.321 3_5C型R3.0530230 6.970 2.1KCR-800C7.321 3_6C型R3.0630230 6.970 2.1KCR-800C7.321 3_7C型R3.0730230 6.970 2.1KCR-800C7.321 3_8C型R3.0830230 6.970 2.1KCR-800C7.321 3_9B型R3.09342307.8270 2.38KCR-1000C9.481 3_10B型R3.10332307.5

11、970 2.31KCR-1000C9.481 3_11C型R3.114523010.3570 3.15KCR-1200C11.51 3_12D型R3.128023018.470 5.6KCR-1200C11.52 3_13B型R3.13332307.5970 2.31KCR-1000C9.481 3_14B型R3.14342307.8270 2.38KCR-1000C9.481 3_15A型R3.1530230 6.970 2.1KCR-800C7.321 3_16A型R3.16392308.9770 2.73KCR-1000C9.481 3_17A型R3.17392308.9770 2.73

12、KCR-1000C9.481 3_18A型R3.18392308.9770 2.73KCR-1000C9.481 3_19A型R3.19392308.9770 2.73KCR-1000C9.481 3_20G型R3.2026230 5.9870 1.82KCR-800C7.3213_21G型R3.21332307.5970 2.31KCR-1000C9.481 3_22G型R3.22322307.3670 2.24KCR-1000C9.481 3_23F型R3.2337.52308.62570 2.625KCR-1000C9.481 3_24F型R3.2431.52307.24570 2.20

13、5KCR-1000C9.481 3_25F型R3.25382308.7470 2.66KCR-1000C9.481 3_26A型R3.2629230 6.6770 2.03KCR-800C7.321 3_27E型R3.27422309.6670 2.94KCR-1200C11.51 3_28E型R3.284923011.2770 3.43KCR-1400C12.91 3_29C型R3.2929230 6.6770 2.03KCR-800C7.321 3_30C型R3.3029230 6.6770 2.03KCR-800C7.321 3_31E型R3.3144.523010.23570 3.11

14、5KCR-1200C11.51 3_32C型R3.3229230 6.6770 2.03KCR-800C7.321 3_33C型R3.3327230 6.2170 1.89KCR-800C7.321 3_34C型R3.3428230 6.4470 1.96KCR-800C7.321 3_35A型R3.354723010.8170 3.29KCR-1200C11.51外廊449新風(fēng)降溫至24度70四層:4_1A型R4.0128.67120 3.440470 2.0069KCR-400C41 4_2A型R4.0228.6120 3.43270 2.002KCR-400C41 4_3A型R4.032

15、8.67120 3.440470 2.0069KCR-400C41 4_4A型R4.0428.6120 3.43270 2.002KCR-400C41 4_5A型R4.0528.67120 3.440470 2.0069KCR-400C41 4_6A型R4.0628.6120 3.43270 2.002KCR-400C41 4_7A型R4.0728.67120 3.440470 2.0069KCR-400C41 4_8A型R4.0828.6120 3.43270 2.002KCR-400C41 4_9A型R4.0928.67120 3.440470 2.0069KCR-400C41 4_10A

16、型R4.1028.22120 3.386470 1.9754KCR-400C41 4_11A型R4.1128.59120 3.430870 2.0013KCR-400C414_12A型R4.1227.71120 3.325270 1.9397KCR-400C41 4_13A型R4.1322.84120 2.740870 1.5988KCR-400C41 4_14A型R4.1424.36120 2.923270 1.7052KCR-400C41 4_15A型R4.1528.4120 3.40870 1.988KCR-400C41 4_16A型R4.1628.4120 3.40870 1.988K

17、CR-400C41 4_17A型R4.1761.811207.417270 4.3267KCR-1000C9.481 4_18A型R4.1828.7120 3.44470 2.009KCR-400C41 4_19A型R4.1927.54120 3.304870 1.9278KCR-400C41 4_20A型R4.2028.7120 3.44470 2.009KCR-400C41 4_21A型R4.2127.54120 3.304870 1.9278KCR-400C41 4_22A型R4.2242.63120 5.115670 2.9841KCR-600C 5.81 4_23布草23.36000

18、4_24中餐大廳519.32300155.7967036.3524KDC070-4424外廊452新風(fēng)降溫至24度28五層:5_1A型R5.141.34120 4.960870 2.8938KCR-600C 5.81 5_2A型R5.228.67120 3.440470 2.0069KCR-400C41 5_3A型R5.328.6120 3.43270 2.002KCR-400C41 5_4A型R5.428.67120 3.440470 2.0069KCR-400C41 5_5A型R5.528.6120 3.43270 2.002KCR-400C41 5_6A型R5.628.67120 3.4

19、40470 2.0069KCR-400C41 5_7A型R5.728.6120 3.43270 2.002KCR-400C41 5_8A型R5.828.67120 3.440470 2.0069KCR-400C41 5_9A型R5.928.6120 3.43270 2.002KCR-400C41 5_10A型R5.1028.67120 3.440470 2.0069KCR-400C41 5_11A型R5.1128.22120 3.386470 1.9754KCR-400C41 5_12A型R5.1231.79120 3.814870 2.2253KCR-400C41 5_13A型R5.1333

20、.05120 3.96670 2.3135KCR-400C41 5_14A型R5.1431.37120 3.764470 2.1959KCR-400C415_15A型R5.1528.59120 3.430870 2.0013KCR-400C41 5_16A型R5.1627.71120 3.325270 1.9397KCR-400C41 5_17A型R5.1722.84120 2.740870 1.5988KCR-400C41 5_18A型R5.1824.36120 2.923270 1.7052KCR-400C41 5_19A型R5.1928.4120 3.40870 1.988KCR-400

21、C41 5_20A型R5.2028.4120 3.40870 1.988KCR-400C41 5_21A型R5.2161.811207.417270 4.3267KCR-1000C9.481 5_22A型R5.2228.7120 3.44470 2.009KCR-400C41 5_23A型R5.2327.54120 3.304870 1.9278KCR-400C41 5_24A型R5.2428.7120 3.44470 2.009KCR-400C41 5_25A型R5.2527.54120 3.304870 1.9278KCR-400C41 5_26A型R5.2642.63120 5.1156

22、70 2.9841KCR-600C 5.81 5_27布草23.36外廊258新風(fēng)降溫至24度26六層:6_1A型R5.141.34120 4.960870 2.8938KCR-600C 5.81 6_2A型R5.228.67120 3.440470 2.0069KCR-400C41 6_3A型R5.328.6120 3.43270 2.002KCR-400C41 6_4A型R5.428.67120 3.440470 2.0069KCR-400C41 6_5A型R5.528.6120 3.43270 2.002KCR-400C41 6_6A型R5.628.67120 3.440470 2.00

23、69KCR-400C41 6_7A型R5.728.6120 3.43270 2.002KCR-400C41 6_8A型R5.828.67120 3.440470 2.0069KCR-400C41 6_9A型R5.928.6120 3.43270 2.002KCR-400C41 6_10A型R5.1028.67120 3.440470 2.0069KCR-400C41 6_11A型R5.1128.22120 3.386470 1.9754KCR-400C41 6_12A型R5.1231.79120 3.814870 2.2253KCR-400C41 6_13A型R5.1333.05120 3.9

24、6670 2.3135KCR-400C41 6_14A型R5.1431.37120 3.764470 2.1959KCR-400C416_15A型R5.1528.59120 3.430870 2.0013KCR-400C41 6_16A型R5.1627.71120 3.325270 1.9397KCR-400C41 6_17A型R5.1722.84120 2.740870 1.5988KCR-400C41 6_18A型R5.1824.36120 2.923270 1.7052KCR-400C41 6_19A型R5.1928.4120 3.40870 1.988KCR-400C41 6_20A型

25、R5.2028.4120 3.40870 1.988KCR-400C41 6_21A型R5.2161.811207.417270 4.3267KCR-1000C9.481 6_22A型R5.2228.7120 3.44470 2.009KCR-400C41 6_23A型R5.2327.54120 3.304870 1.9278KCR-400C41 6_24A型R5.2428.7120 3.44470 2.009KCR-400C41 6_25A型R5.2527.54120 3.304870 1.9278KCR-400C41 6_26A型R5.2642.63120 5.115670 2.9841K

26、CR-600C 5.81 6_27布草23.36外廊258新風(fēng)降溫至24度26七層:7_1客房117.21230 3.958370 1.2047KCR-400C41 7_2客房225230 5.7570 1.75KCR-600C 5.81 7_3客房319.32230 4.443670 1.3524KCR-600C 5.81 7_4總統(tǒng)套房外區(qū)11.3200007_5客廳44.8223010.308670 3.1374KCR-1200C11.51新風(fēng)由風(fēng)機(jī)盤(pán)管直接引入1717.4707487.5262慕蘭酒店空調(diào)及熱水系統(tǒng)方案一、設(shè)計(jì)概況該建筑位于廣東惠州市,設(shè)計(jì)為集酒店大堂、客房、餐廳、KT

27、V、沐足等為一體的綜合性酒店。建筑面積約12000平方米,空調(diào)房間面積約為7500平方米,空調(diào)走廊面積約為2050平方米(此區(qū)域送處理過(guò)的新風(fēng)即可,空調(diào)總面積約為9550平方米(注,上述依據(jù)為設(shè)計(jì)圖紙,可能存在一定誤差。各區(qū)域空調(diào)負(fù)荷參數(shù)表詳見(jiàn)附表。熱水方面,主要用水點(diǎn)位于37層。該酒店衛(wèi)生熱水工程范圍:全天24小時(shí)為該樓內(nèi)沐足房間、客房、衛(wèi)生間洗手提供50-55衛(wèi)生熱水。根據(jù)該酒店的特點(diǎn),建議采用水冷螺桿機(jī)組+多功能模塊機(jī)組+冷暖型風(fēng)冷模塊機(jī)組,以保證酒店的制冷、熱水、制熱都在最經(jīng)濟(jì)、節(jié)能的工況下運(yùn)行。二、設(shè)計(jì)依據(jù)1.采暖通風(fēng)與空氣調(diào)節(jié)設(shè)計(jì)規(guī)范(GB50019-2003;2.建筑給水排水設(shè)計(jì)

28、規(guī)范(GB50015-2003;3.室外給水設(shè)計(jì)規(guī)范(GBJ1386;4.給水排水制圖標(biāo)準(zhǔn)(T50106-2001;5.建筑設(shè)計(jì)防火規(guī)范(GBJ16872001;6.建設(shè)單位的要求。三、相關(guān)設(shè)計(jì)標(biāo)準(zhǔn)1、室外環(huán)境設(shè)計(jì)計(jì)算參數(shù)夏季:干球溫度:33.5濕球溫度:27.7冬季:干球溫度:5濕球溫度:1.32、室內(nèi)環(huán)境設(shè)計(jì)計(jì)算參數(shù)夏季:溫度:24+2冬季:溫度:20+23、熱水設(shè)計(jì)計(jì)算參數(shù)(以冬季為標(biāo)準(zhǔn)冷水計(jì)算溫度:5熱水計(jì)算溫度:55四、負(fù)荷分項(xiàng)設(shè)計(jì)計(jì)算及分析說(shuō)明附表中對(duì)各區(qū)域作了分別統(tǒng)計(jì)計(jì)算,下邊針對(duì)各主要的功能區(qū)域進(jìn)行分析及必要的計(jì)算,以便進(jìn)行綜合節(jié)能考慮,其中走廊等輔助區(qū)域空調(diào)量小,不作詳細(xì)分析

29、。1、空調(diào)制冷方面:餐廳(包括一樓大廳、一樓茶餐廳、二樓包房、四樓中餐大廳:總負(fù)荷約為1122KW 餐廳的空調(diào)負(fù)荷特點(diǎn)為:1負(fù)荷大,而且負(fù)荷集中在短時(shí)間內(nèi),需要大冷量進(jìn)行及時(shí)的降溫處理;2人員密度大,必須進(jìn)行足夠的新風(fēng)量補(bǔ)充和足夠的換氣,以保證人體的舒適度;3負(fù)荷波動(dòng)大,因客流的情況室內(nèi)負(fù)荷在客流高峰及少客流階段的負(fù)荷差異很大,所以空調(diào)系統(tǒng)即要滿足瞬間負(fù)荷量大增的需要,也要能實(shí)現(xiàn)負(fù)荷量小時(shí)的低冷量輸出,以達(dá)到節(jié)能效果。4高負(fù)荷的出現(xiàn)時(shí)間穩(wěn)定可控,一般出現(xiàn)在中午午餐時(shí)間(11:30-13: 30,晚飯時(shí)間(18:30-19:30針對(duì)餐廳上述特點(diǎn),室內(nèi)空調(diào)設(shè)計(jì)采用若干大風(fēng)量的吊掛式空調(diào)機(jī)組,以滿足

30、室內(nèi)相關(guān)要求,同時(shí)新風(fēng)系統(tǒng)與其它區(qū)域分開(kāi),由吊掛式空調(diào)機(jī)組直接引入,如此即可以滿足餐廳要求,也可以節(jié)約餐廳不營(yíng)業(yè)時(shí)因新風(fēng)機(jī)組而消耗的大量能源。沐足房(二樓:總負(fù)荷約為90KW沐足房負(fù)荷的特點(diǎn):1負(fù)荷不大,但因有熱水的使用會(huì)使客人有要求降低溫度的要求,因此必須適當(dāng)加大末端的冷量使用;2高負(fù)荷的出現(xiàn)時(shí)間穩(wěn)定可控,一般出現(xiàn)在中午午餐時(shí)間之后(13:00-14:30,晚飯時(shí)間之后(18:30-次日2:00針對(duì)餐廳上述特點(diǎn),室內(nèi)空調(diào)設(shè)計(jì)采用風(fēng)機(jī)盤(pán)管,可以靈活根據(jù)房間的使用情況開(kāi)啟、關(guān)閉、調(diào)節(jié)相關(guān)設(shè)備,相關(guān)設(shè)備適當(dāng)選備大;另配置新風(fēng)系統(tǒng)。KTV房(三樓:總負(fù)荷約為326KWKTV房負(fù)荷的特點(diǎn):1負(fù)荷較大,

31、人員密度較大,需要大冷量進(jìn)行及時(shí)的降溫處理及足夠新風(fēng)量的補(bǔ)充;2高負(fù)荷的出現(xiàn)時(shí)間穩(wěn)定可控,一般出現(xiàn)在晚飯時(shí)間之后(18: 30-次日2:00針對(duì)餐廳上述特點(diǎn),室內(nèi)空調(diào)設(shè)計(jì)采用風(fēng)機(jī)盤(pán)管,可以靈活根據(jù)房間的使用情況開(kāi)啟、關(guān)閉、調(diào)節(jié)相關(guān)設(shè)備,相關(guān)設(shè)備適當(dāng)選備大;另配置新風(fēng)系統(tǒng)??头?四-七樓:總負(fù)荷約為322KW客房房負(fù)荷的特點(diǎn):1負(fù)荷很小,人員密度很低;2高負(fù)荷的出現(xiàn)時(shí)間不可控。針對(duì)餐廳上述特點(diǎn),室內(nèi)空調(diào)設(shè)計(jì)采用風(fēng)機(jī)盤(pán)管,可以靈活根據(jù)房間的使用情況開(kāi)啟、關(guān)閉、調(diào)節(jié)相關(guān)設(shè)備,相關(guān)設(shè)備適當(dāng)選備小;另配置新風(fēng)系統(tǒng)。2、空調(diào)采暖方面:最大總負(fù)荷約為487KW因南方氣候較為暖和,各功能區(qū)域只作適當(dāng)溫度補(bǔ)償即

32、可滿足人體舒適性需要,因采暖要求并不高,新風(fēng)的要求特點(diǎn)與制冷情況相同,且室內(nèi)制冷使用的相關(guān)設(shè)備完全可滿足采暖使用,這里不作分區(qū)的詳細(xì)分析。3、生活熱水方面1沐足房:有86個(gè)位置(按每天12小時(shí),每小時(shí)40L/位計(jì)算2客房:有83個(gè)(按每個(gè)房間2人,每人100L計(jì)算3衛(wèi)生間:洗手用水沐足房需要用水量=40*12*86=41280L客房房需要用水量=100*2*83=16600L衛(wèi)生間用水量很小,同時(shí)考慮沐足房及客房的不同時(shí)使用系數(shù),對(duì)此部分不作統(tǒng)計(jì),只在下邊機(jī)組總選型的時(shí)候作余量處理。熱水所需熱量Qh=Ld(tr-tl=(41280+16600(55-5=2894000kcal式中Ld-設(shè)計(jì)日熱

33、水用量(m3;m-用水計(jì)算單位數(shù)(人;qr-設(shè)計(jì)用熱水定額(L;tr-熱水計(jì)算溫度(;tl-冷水計(jì)算溫度(;Qh-設(shè)計(jì)日耗熱量(kcal) ; 設(shè)備平均所需要制熱能力(每天額定工作 18 小時(shí)計(jì)算) : Qh86020=289400086020=168KW 同理: 夏季熱水所需熱量 Qh2= Ld( trt2)=( 41280+16600)(5520=2025800kcal 設(shè)備制熱能力:Qh286020=289400086020=130KW 五、負(fù)荷綜合分析說(shuō)明及空調(diào)機(jī)組選型 從上述分析可以看到, 1、夏季空調(diào)冷負(fù)荷: 全天最大負(fù)荷率應(yīng)該出現(xiàn)在中午午飯時(shí)間,此時(shí)負(fù)荷應(yīng)該以餐廳為主,交錯(cuò)有沐足

34、房、 相關(guān)一樓其它商業(yè)區(qū)域及部分客房的使用。此時(shí)總冷負(fù)荷 QA 應(yīng)為: (餐廳+沐足*0.3+客房 *0.5+其它商業(yè)區(qū)域) QA=1122+90*0.3+322*0.5+100=1410KW 全天中第二大空調(diào)高峰期出現(xiàn)在晚飯時(shí)間此時(shí)負(fù)荷應(yīng)該以餐廳為主, 交錯(cuò)有沐足房、 KTV 房間相關(guān)一樓其它商業(yè)區(qū)域及部分客房的使用。此時(shí)總此時(shí)總冷負(fù)荷應(yīng) QB 為: (餐廳*0.8+ 沐足*0.2+KTV 房*0.1+客房*0.4+其它商業(yè)區(qū)域*0.5) QB=1122*0.8+90*0.2+326*0.1+322*0.4+100*0.5=1127KW 第三大空調(diào)高峰期出現(xiàn)在晚間休息時(shí)間,應(yīng)為沐足房、KTV

35、 房間、及客房集體啟動(dòng)。 此 時(shí)負(fù)荷 QC 應(yīng)為: (沐足房+KTV 房+客房) QC=90+326+322=738KW 其它大部分時(shí)間以客房及其它商業(yè)區(qū)域的使用為主。負(fù)荷 QD 為: (客房*0.8+其它商業(yè) 區(qū)域) QD=322*0.8+100=357.6KW 2、熱水使用方面: 在前邊計(jì)算中我們可以看到,熱水設(shè)備平均熱水量必須大于 168KW。考慮到冬季晚飯前 4 后熱水的大量使用,主要為客房洗澡用水及沐足用水集中大量增加,選型時(shí)必須充分考慮此 時(shí)熱水需求量大增問(wèn)題。 夏季:空調(diào)機(jī)組的熱回收須可滿足熱量的補(bǔ)充 冬季:熱水機(jī)組的制熱須可滿足熱量的補(bǔ)充 3、機(jī)組選型及運(yùn)行分析 推薦采用滿液式

36、螺桿冷水機(jī)組(帶熱回收)+多功能模塊機(jī)組+冷暖型風(fēng)冷模塊機(jī)組 (總冷量達(dá)到 1505KW,夏季最大熱水熱量達(dá)到 568KW,冬季達(dá)到 252KW,系統(tǒng)最大制熱量 504KW) 滿液式螺桿冷水機(jī)組采用 525KW(熱回收量 158KW)兩臺(tái) 多功能機(jī)組(65KW 制冷量,熱水制熱量 82KW、制熱量 72KW)三臺(tái) 冷暖型風(fēng)冷模塊機(jī)組(65KW 制冷量,制熱量 72KW)四臺(tái) 使用運(yùn)行分析 1)夏季方面,制冷系統(tǒng)啟動(dòng)后,系統(tǒng)將優(yōu)先投入兩臺(tái)滿液式螺桿冷水機(jī)組(總制冷量 為 525*2KW)進(jìn)行制冷,同時(shí)進(jìn)行熱量的存貯,這樣可以使系統(tǒng)在最節(jié)能的狀況下運(yùn)行; 兩 螺桿機(jī)組的制冷量的要求后,自動(dòng)投入運(yùn)行

37、多功能熱水機(jī)(冷量 65KW*3)進(jìn)行制冷,也可 以同時(shí)進(jìn)行熱量的存貯; 若此時(shí)還達(dá)不到系統(tǒng)制冷量的要求, 再開(kāi)啟冷暖型風(fēng)冷模塊機(jī)組 (冷 量 65KW*4) ,直到達(dá)到系統(tǒng)所需制冷量為止。 如:前邊提到最大負(fù)荷 QA 狀態(tài)時(shí)(總需求約為 1410KW) ,系統(tǒng)將自動(dòng)投入兩臺(tái)螺桿冷 水機(jī)組(共 1050KW) ,三臺(tái)多功能熱水機(jī)組(共 195KW) ,再投入 2.5 臺(tái)模塊式冷水機(jī)組 (162.5KW,注模塊機(jī)由兩壓縮機(jī)組成,為可以開(kāi)啟一半機(jī)組以適應(yīng)系統(tǒng)冷量要求) 再如:前邊提到的負(fù)荷第二高峰期 QB 狀態(tài)時(shí)(總需求為 1127KW) ,系統(tǒng)系統(tǒng)將自動(dòng)投 入兩臺(tái)螺桿冷水機(jī)組(共 1050KW) ,一臺(tái)多功能熱水機(jī)組(共 65KW) 。 2)夏季方面,當(dāng)系統(tǒng)負(fù)載減小時(shí),系統(tǒng)將優(yōu)先關(guān)閉冷暖型風(fēng)冷模塊機(jī)組,再關(guān)閉多功 能熱水機(jī)組,最后調(diào)節(jié)或關(guān)閉螺桿冷水機(jī)組,以保證機(jī)組在最節(jié)能的狀況下運(yùn)行。 3)在熱水方面,若螺桿式冷水機(jī)組或多功能熱水機(jī)組在運(yùn)行,系統(tǒng)自動(dòng)對(duì)空調(diào)使用中 的熱量進(jìn)行回收貯存,直到溫度達(dá)到設(shè)定值為止(設(shè)計(jì) 55 度

溫馨提示

  • 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

評(píng)論

0/150

提交評(píng)論